How to Determine the Number of Lighting Branch Circuits?
How to Determine the Number of Lighting Branch Circuits for Dwelling and Non-Dwelling Units – NEC 2023
According to NEC Article 100 – Definitions, a branch circuit refers to the conductors between the overcurrent protection device and the final circuit element, such as an outlet. A general-purpose branch circuit supplies more than one outlet or receptacle for general lighting purposes. Furthermore, an individual branch circuit is defined as a branch circuit that supplies power to only one specific piece of utilization equipment.
In the following step by step guide, we will show how to know the number of general-purpose lighting branch circuits in a dwelling and non-dwelling building with solved example based on NEC-2023.
- Related Posts: How to Determine the Number of Branch Circuits? – 3 Ways
Click image to enlarge or open in a new window
Lighting Branch Circuits in a Dwelling Unit
To determine the number of lighting branch circuits required in the dwelling and non-dwelling units, the National Electrical Code (NEC) 2023 provides specific guidelines in Article 220 and associated tables for branch circuits and lighting load for specified occupancies.
Article 220.41 specifies that the minimum load requirement for a dwelling unit is 3 VA (Volt-Amperes) per square foot (3 VA/ft2), which shall not be less than 33 VA/m2 of occupied area.
Based on these values, the minimum requirements are as follows this equals to:
- One 15-Amp lighting branch circuit for every 600 ft2.
- One 20-Amp lighting branch circuit for every 800 ft2.
Since 20-Amp branch circuits are uncommon for lighting in residential units, we typically use 15-Amp lighting branch circuits.
Example 1
The following formulas can be used to determine the minimum number of 15-Amp lighting branch circuits required for a residence:
Suppose the total occupied area of a single-family unit with a basement is 3,000 ft² (278.7 m2). To find the total amperes required:
Amperes = (3VA × ft2) / 120V
(3VA × 3000 ft2) / 120V = 75-Amp
Now, Divide the calculated amperes by the rated amperes of the branch circuit (15 Amps).
Min. number of 15A lighting branch circuits = Amperes ÷ 15A
= 75A ÷ 15A
= 5
Alternatively, you may divide the total area in ft2 by 600 ft2 to get the number of 15A lightning branch circuits, and hence, will get the same answer i.e. 5.
Alternatively, you can divide the total area in ft2 by 600 ft2 to get the number of 15-Amp lighting branch circuits. The result will be same as above
3000 ft2 ÷ 600 ft2 = 5
Thus, the total number of required lighting branch circuits for a dwelling unit with a total occupied area of 3,000 ft2 is 5.
Lighting Branch Circuits For Non-dwelling Unit
The general lighting load for non-dwelling units (where the VA/ft2 or VA/m2 differs from that of a dwelling unit) with floor area determined by 220.5(C) can be calculated using Table 220.42(A). If the total load exceeds 3 kVA, a demand factor specified in Table 220.45 applies to the total branch circuit load for illumination. However, this is not applicable when determining the number of branch circuits for general lighting.
Example 1: Office Space
Given:
-
- Area = 3,000 ft2
- Lighting load = 1.3 VA/ft2 (from NEC 2023 Table 220.41(A) for office buildings)
- Voltage = 120V
- Circuit Breaker = 15A
Steps:
1. Total Lighting Load:
3,000 ft2 × 1.3 VA / ft2 = 3,900 VA
2. Circuit Capacity:
Maximum load per circuit: 15A × 120V × 0.8 = 1,440 VA
3. Number of Branch Circuits:
Divide total load by capacity:
3,900 VA /1,440 VA = 2.7 circuits
Which is round up to 3 circuits.
Example 2: Retail Store
Given:
-
- Area = 2,500 ft2
- Lighting load = 1.9 VA/ft2 (from Table 220.41(A) for retail spaces)
- Voltage = 277V (common in commercial buildings)
- Circuit Breaker = 20A
Steps:
1. Total Lighting Load:
2,500 ft2 × 1.9 VA/ft2 = 4,750 VA
2. Circuit Capacity:
Maximum load per circuit:
20A × 277V × 0.8 = 4,432 VA
3. Number of Circuits:
Divide total load by circuit’s capacity:
4,750 VA / 4,432 VA/circuit = 1 circuit.
- NEC 210.11(A): The minimum number of branch circuits shall be determined by the size or rating of the circuit based on the total calculated load.
- NEC 210.11(B): Loads calculated based on VA/ft2 or VA/m² shall be evenly divided among multi-outlet branch circuits supplied by the panelboard(s).
- The load calculation includes all general-purpose 20-Amp outlets and receptacles as specified in NEC 210.11(B), 210.52(E) & (G), and 210.70.
- Motors rated below 0.5 HP are considered part of the general lighting circuit.
- In all installations, the number of circuits shall be sufficient to supply the load served. In no case shall the load on any circuit exceed the maximum determined by Article 220.11.
- NEC 240.4(D) specifies the maximum overcurrent protection ratings for conductors:
- 15-Amp for 14 AWG Copper or 12 AWG Aluminum
- 20-Amp for 12 AWG Copper or 10 AWG Aluminum
- 30-Amp for 10 AWG Copper
Resources:
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Determine the Right Size Capacity of a Subpanel?
- How to Determine the Suitable Size of Inverter for Home Appliances?
- How to Calculate the Number of Panels for a Load without Battery Backup?
- How to Find the Right Wire Size for 100A Service 120V/240V Panel?
- How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation? (Metric & Imperial Systems)
- How to Find Voltage & Ampere Rating of Switch, Plug, Outlet & Receptacle
- How to Determine the Number of Incandescent Lamps in a Final Sub Circuit?
- How to Calculate the Number of Fluorescent Lamps in a Final Sub Circuit?
- How to Size and Find the Numbers of Ceiling Fan in a Room?
- How to Size a Generator? Portable, Backup & Standby for Home & Commercial Applications
- How to Size Earth Conductor, Earthing Lead and Earth Electrodes?
- How to Size a Single Phase and Three Phase Transformer in kVA? Calculator
- Lighting Design Calculation in a Building – Step by Step Guide
- Public Street & Road Lighting & Illumination Design
- What is Energy Efficient Lighting and Techniques to Implement It
- Star and Delta Connected Lighting Loads