Amps to kVA Calculator – How to Convert Amps to kVA?
How to Convert Amps to kVA – Calculator and Examples
Amps to kVA Calculator
The following Amps to KVA conversion calculator will convert the current “I” in amperes “A” to apparent power “S” in kVA “kilovolt amperes”, VA “volt-amp”, mVA “millivolt amps” and MVA “mega volt amp”.
To calculate the kVA rating of a machine from the amperage rating, just enter the value of current in amperes, voltage in volts, select power supply system (single phase or three phase) and hit the “Calculate” button to the get the result of apparent power in kVA, VA, mVA and MVA.
Related Calculators:
- Amps to Watts Calculator & Conversion – DC/AC (1 & 3 Phase)
- Watts to Amps Calculator & Conversion – DC/AC (1 & 3 Phase)
Amps to kVA Conversion Formulas & Equations
Single Phase Current in Amps to kVA Conversion
S = V x I ÷ 1000
kVA = Volts x Amps ÷ 1000
Three Phase Current in Amps to kVA Conversion
Conversion with Line to Line Voltage (VL-L)
S = √3 x VL-L x I ÷ 1000
kVA = (1.732 x VL-L x I) ÷ 1000
Conversion with Line to Neutral Voltage (VL-N)
kVA = S = 3 x VL-N x I ÷ 1000
Where:
- S = Apparent Power in Volt-Amps
- V = Voltage in Volts
- I = Current in Amperes
- VL-L = Line to Line Voltage in 3-Phase Circuits
- VL-N = Line to Neutral Voltage in 3-Phase Circuits
Note: There is no concept of apparent power in DC circuits as there is no frequency, power factor and reactive power exists in DC supply systems.
Related Posts:
- Electric Energy Cost Calculator – Cost of Energy Calculation
- Energy and Power Consumption Calculator – kWh Calculator
How to Convert Amps to kVA?
Keep in mind that you must know the value of current and voltage to calculate the kVA rating of a machine.
Single Phase Amps to kVA Calculation
Apparent Power in kVA = (Voltage in Volts x Current in Amperes) ÷ 1000
S = (V x I) ÷ 1000
Example:
Find the kVA rating of a single phase transformer if the primary current rating is 120 amperes and RMS voltage is 120V.
Solution:
S = (120V x 125A) ÷ 1000
kVA = S = 15kVA
Three Phase Amps to kVA Calculation
Calculation with Line to Line Voltage
Apparent Power in kVA = (√3 x Voltage in Volts x Current in Amperes) ÷ 1000
S = (√3 x VL-L x I) ÷ 1000
Example:
Calculate the apparent power in kVA if the value of current is 28A and RMS voltage is 208V (line to line) three phase.
Solution:
S = (1.732 x 208V x 28A) ÷ 1000
kVA = S = 10kVA
Calculation with Line to Neutral Voltage
Apparent Power in kVA = (3 x Voltage in Volts x Current in Amperes) ÷ 1000
S = (3 x VL-N x I) ÷ 1000
Example:
Calculate the rating of three phase transformer if the rating of three phase RMS voltage is 240V (line to neutral) and primary current is 25 amperes.
Solution:
S = (3 x 240V x 25A) ÷ 1000
kVA = S = 18kVA
Related Electrical and Electronic Engineering Calculators:
- Circuit Breaker Size in Amps Calculator
- Electrical Wire & Cable Size Calculator (Copper & Aluminum)
- Wire & Cable Size Calculator in AWG
- Advance Voltage Drop Calculator and Voltage Drop Formula
- Power, Voltage, Current & Resistance (P,V,I,R) Calculator
- Required Value of Resistor for LED’s Circuit Calculator
- 3, 4, 5 and 6 Band Resistor Color Code Calculators
- RMS Voltage Calculator
- Voltage Divider Rule (VDR) Calculator
- Battery Capacity Rating Calculator
- Electricity Bill Calculator – How to Calculate your Electric Bill – Examples
I hope to learn much more while using this flatform