Relay
-
Control
How to Wire One-Shot Timer using Twin Timer For Delay?
Wiring Twin Timer for One-Shot Operation of Recirculation Pump What is a One-Shot Timer? As the name suggests, it performs a single operation per signal activation instead of repeated cycle…
Read More » -
Control
How to Wire ST01 Timer with Relay & Contactor for 120V/240V Motors?
How to Control 120V & 240V Pump Motor using ST01 Timer, Relay and Contactors? As a versatile component, the ST01 timer can be used to control the sequential operations of…
Read More » -
Control
How to Wire Spring Wound Timer with LYS Rely for ON/OFF Delay
Wiring a Spring Wound Timer with an LY2 Surface Mount Relay for ON-Delay and OFF-Delay Operations In today’s wiring tutorial, we will demonstrate how to wire a spring-wound timer for…
Read More » -
Control
How to Wire AH3 OFF-Delay Timer and Relay with Boiler Fan?
Wiring AH3-3 Timer for OFF-Delay Operation with Boiler and Fan The main purpose of the circuit is to automatically turn off the wall fan when the boiler switches off, using…
Read More » -
Control
3-Phase Automatic Changeover (ATS) using Contactors and Timer
Automatic Changeover Switch (ATS) Connection using Contactors, Timer And Relay for 3-Phase Load Automatic changeover switches play a crucial role in ensuring uninterrupted power supply in various industrial, commercial and…
Read More » -
Control
1-Phase Automatic Changeover (ATS) using Contactors and Timer
How to Wire an Automatic Changeover Switch (ATS) using Contactors and Timer for Single-Phase Load? An Automatic Transfer Switch (ATS) is a critical component in ensuring uninterrupted power supply in…
Read More » -
Control
Automatic Phase Reverse Protection Using Contactors & Relay
Auto Phase Sequence Failure Panel using Contactors and Phase Sequence Protection Relay Phase reverse protection is a critical aspect of electrical systems, particularly in three-phase power distribution networks and connected…
Read More » -
Control
Automatic ON/OFF Circuit Using Two 8-PIN Timers for 1 & 3-Φ Load
Automatic Start & Stop Circuit for 1-Phase Load and 3-Phase Motors Using two 8-PIN Timers Automating the operation of 3-phase motors or single phase load in industrial setups brings efficiency…
Read More » -
Control
ON / OFF 3-Phase Motor Using 14-PIN Relay and DOL Starter
How to Start and Stop a Three-Phase Motor using 14-PIN PLA Relay and DOL Starter? Controlling a 3-phase motor using a DOL starter is the simplest method among others, such…
Read More » -
Control
ON / OFF 3-Phase Motor Using 11-PIN Relay and DOL Starter
How to Start and Stop a Three-Phase Motor using 11-PIN PLA Relay and DOL Starter? There are various methods for controlling, starting, and stopping three-phase motors, such as Star-Delta Starter,…
Read More »