What Happens if the Neutral is Lost in the Main or Subpanel?
What Will Happen When the Neutral is Broken in the Main Panel or Subpanel?
The neutral wire provides a return path for current back to the power source, completing the electric circuit. It is insulated and carries current under normal conditions back to the transformer. According to NEC standards, the color used for neutral wires is white, while IEC and BS7671 standards use light blue. In today’s post, we will discuss the hazardous effects of a lost neutral in the main disconnect, main panel, or remote subpanel.
- Related Posts: Why are Neutral and Ground Wires Separated in a Subpanel?
- Related Posts: Why Must Neutral and Ground Wires Be Bonded in the Main Panel?
If the neutral connection is lost or broken in the main panel, several critical issues can arise:
- Unbalanced Voltage Across Circuits: Without a neutral, the 240V supply remains active, but 120V circuits can become unstable. This instability can lead to unbalanced voltage, where one side of the circuit may receive a higher voltage than the other. Appliances and devices connected to these circuits can experience overvoltage or undervoltage, potentially damaging sensitive electronics or causing them to malfunction.
- Flickering or Dimming Lights: In some cases, lights may flicker, dim, or brighten unexpectedly due to fluctuating voltages across circuits. This is a common sign of a broken neutral and can be hazardous if left unaddressed.
- Increased Risk of Electrical Fire: If the voltage fluctuates excessively, it can cause wires, connectors, or devices to overheat. This overheating can lead to insulation breakdown and, in extreme cases, electrical fires.
- Electric Shock Hazard: Without a stable neutral, certain metal parts connected to the electrical system may become energized, posing an electric shock risk.
Hazardous Consequences of a Missing Neutral in the Panel
Case 1 – Absence of Neutral in the Main Panel
Suppose the neutral is lost in the service equipment (main panel) or service disconnect. In a ground fault condition, current flows back from the load to the neutral bar in the remote distribution panel (subpanel), which is connected to the neutral terminal busbar in the main panel. Since the neutral and ground terminal busbars must be bonded in the main panel or first service disconnect, current now flows back to the supply source (i.e., transformer) through the equipment grounding conductor and ground rod, as it is the only available return path.
Click image or open in new tab to enlarge
If the load resistance is 20Ω and the grounding path to the transformer has 30Ω of resistance, the returning current will be 2.4 amps, forming a series circuit:
- I = V ÷ R
- I = 120V ÷ (20Ω + 30Ω)
- I = 120V ÷ 50Ω
- I = 2.4 Amp
This 2.4-amp current may not trip a standard 15- or 20-amp breaker. To trip the breaker, a GFCI breaker is needed because it senses unbalanced current in the neutral. If it detects that the current in the hot and neutral wires is not the same, it will immediately trip and disconnect the circuit to ensure personal safety.
Since the supply voltage is 120V, assume the resistances of the load and ground path to the transformer are 20Ω and 30Ω, respectively. Therefore, the output voltage in the circuit is:
- VOut = (VIn × R2) ÷ (R1 + R2)
- VOut = (120V × 30Ω) ÷ (20Ω + 30Ω)
- VOut = (120V × 30Ω) ÷ (20Ω + 30Ω)
- VOut = (3,600) ÷ (50Ω)
- VOut = 72V
The circuit is still working but the light is dim with flickering. This way, all metal parts in the above circuit are energized with 72V.
If there is no subpanel used, the circuit will look like this:
Case 2 – Absence of Neutral in the Main Panel & Phase-to-Ground Fault
Now, consider the same scenario—absence of neutral in the main panel—but with an additional fault where the hot wire touches a metallic part of the device, such as a bulb holder.
In this ground fault condition, the returning current takes an incorrect path back to the power source. As shown, the fault current flows through the ground wire, as there is no neutral connection, making the grounding conductor the only available path.
Click image or open in new tab to enlarge
With almost zero load resistance in a short circuit, 4 to 10 amps of current will flow, assuming a 30Ω resistance in the grounding path:
- I = V ÷ R
- I = 120V ÷ 30Ω
- I = 4 Amp
This 4-amp current is insufficient to trip a standard 15- to 20-amp breaker typically used for household appliances in main and subpanels. Therefore, a GFCI breaker is required to address this issue.
In this scenario, the load is off, but all metallic parts, including metal raceways and equipment enclosures, are energized with 120V because they are bonded to the ground terminal.
The case will be similar without a subpanel used in the premises.
Case 3 – Absence of Neutral in the Subpanel
Now, consider another scenario where the neutral is lost in the subpanel while it remains available in the main panel.
This is not a hazardous case because the load is off due to the lack of a neutral connection, similar to other load appliances. However, keep in mind that the neutral wire carries current up to the neutral bar in the subpanel. Touching it may cause electric shock, which is why a GFCI breaker is necessary for added protection.
Click image or open in new tab to enlarge
This explains why the neutral and ground are separated in the subpanel and only bonded in the main panel. If accidental bonding between neutral and ground were to occur, the same issue as described in Case 1 would arise, as the fault current would find a path back to ground.
Resources & Tutorials:
- National Electrical Code (NEC) Requirements for Panelboards
- How to Find the Right Wire Size for 100A Service 120V/240V Panel?
- How to Determine the Right Size Capacity of a Subpanel?
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
- How to Determine the Number of Circuit Breakers in a Panel Board?
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Wire 120V & 240V Main Panel? Breaker Box Installation
- How to Wire 120V & 208V – 1 & 3-Phase Main Panel? 3-Φ Load Center Wiring
- How to Wire 240V, 208V & 120V, 1 & 3-Phase, High Leg Delta Main Panel?
- How to Wire 277V & 480V, 1-Phase & 3-Phase, Commercial Main Service Panel?
- How to Wire and Install an Electrical Outlet Receptacle?
- How to wire a GFCI Outlet?
- How to Wire an AFCI Outlet?
- Single Phase Electrical Wiring Installation in Home according to NEC & IEC
- Three Phase Electrical Wiring Installation in Home – NEC & IEC
- How to Wire Combo Switch and Outlet?
- How to Wire GFCI Combo Switch and Outlet
- How to Wire an AFCI Combo Switch
- How to Wire a GFCI Circuit Breaker?
- How to Wire an AFCI Breaker?
- What Happens When You Touch an Electrical Busbar?
- Why are Electrical Busbars Rectangular Instead of Circular?
- Can the Neutral Wire Cause Electric Shock? Different Cases
- Difference Between Grounding, Earthing and Bonding
- Difference Between Neutral, Ground and Earth?
- Will I Get an Electric Shock If I Touch the Ground Wire?
- Will a Man Get an Electric Shock If He Hangs on a Live Wire?
- Difference Between Circuit Breaker and GFCI
- Tripping Curves of Circuit Breakers – B, C, D, K and Z Trip Curve