How to Determine the Number of Branch Circuits? – 3 Ways

How Many Branch Circuits Do You Need in a Dwelling Unit for Lighting Applications? 3-Methods with Examples

Before determining the required number of circuits and associated calculations, let’s define and differentiate between branch circuits, general-purpose lighting branch circuits, and individual branch circuits.

According to NEC Article 100 – Definitions:

In this step-by-step tutorial, we’ll show how to determine the appropriate number of branch circuits for a dwelling unit using three methods, with solved examples based on NEC 2023.

Related Post: How to Determine the Number of Lighting Branch Circuits?

Click image to enlarge or open in a new window

Service-Entrance, Feeders & Branch Circuits - Article 100 - NEC

1: Outlets per Circuit Method

This method is straightforward and requires no complex calculations. It is commonly used by electricians to estimate the number of branch circuits and the outlets to be connected per circuit in a building.

The method assumes that 1A or 120W is the general-purpose load per outlet, while 1.5A or 180W is used for heavier loads, such as portable tools in a garage. For instance, a 15-amp lighting branch circuit is typically sufficient for a bedroom with 6 receptacles, two closet lights, and a ceiling fan with a light kit. If the load wattage is low, you can add more outlets to the circuit. Conversely, fewer outlets should be connected for higher-wattage loads.

In this method, just count the total number of required outlets and connect maximum of 10 outlets per circuit for low-wattage loads and 15 outlets per circuit for high-wattage loads.

Example:

Determine the required number of 15-amp lighting branch circuits for a dwelling unit with 90 general-purpose lighting and receptacle outlets (to be wired).

Solution:

If the anticipated load is high-wattage, connect 10 outlets per circuit:

90 outlets ÷10= 9 circuits

Hence, you need a minimum of nine 15-amp general-purpose lighting circuits.

If the anticipated load is low-wattage, connect 15 outlets per circuit:

90 outlets ÷15 = 6 circuits

Based on the calculation, you need a minimum of six 15-amp general-purpose lighting circuits.

2: Per Square Foot Method

This method is little bit complicated as calculation are involved. As we know from the previous ‘how-to tutorial’ on determining the number of lighting branch circuits in a dwelling unit, the minimum load requirement is 3 VA (volt-amperes) per square foot (3 VA/ft2), and it shall not be less than 33 VA/m2 of occupied area, as specified in NEC Article 220.41.

For instance, a 600 ft² (55.8 m2) area typically requires one 15-amp branch circuit, while an 800 ft² (74.3 m2) area may require one 20-amp branch circuit. However, 20-amp circuits are less common for residential lighting applications.

Example:

How many 15-amp lighting branch circuits are needed for a house with a 3,000 ft2 occupied area?

Solution:

Divide the total area by 600 ft2 (the approximate area one 15-amp circuit can cover):
3,000 ft2 ÷ 600 ft2 =5 circuits

Based on the calculations, a minimum of five 15-amp general-purpose lighting branch circuits are needed for 3,000 ft² of covered area.

To be on the safe side, you may opt for more than five 15-amp general-purpose lighting branch circuits due to the numerous small-wattage electrical devices and appliances commonly found in homes today.

3: The 80% Rule Method

This method is based on the well-known 80% continuous load rule, detailed in NEC 210.19(A), 210.20(A), 215.2(A), 215.3, and 230.42(A). While primarily intended for commercial and industrial continuous loads (those lasting three hours or more, such as a water heater), applying this rule in residential settings enhances safety.

To use this method, sum the total wattage or amperage of the loads connected to the branch circuit. Limit the connected load to 80% of the circuit’s rated capacity.

For example, consider a 15-amp, 120V lighting branch circuit:

Therefore, a maximum of 12A or 1,440W should be connected to this 15-amp, 120V circuit.

Similarly, for a 20A circuit:

Thus, a maximum of 16A or 1,920W should be connected to a 20-amp, 120V lighting branch circuit.

Good to Know:

Resources:

Exit mobile version