How Do GFCI and Standard Breakers Respond to Ground Faults?
How Does a GFCI Breaker Protect Us in Case of a Fault, Compared to Standard Breakers?
An ordinary circuit breaker in the main panel for household appliances protects only in the event of a short circuit or overload. In contrast, a Ground Fault Circuit Interrupter (GFCI) offers protection against both overload (short circuits) and, more importantly, specific ground fault conditions.
In this article, we’ll explain why a standard breaker cannot protect you in the event of a ground fault and why GFCIs are necessary to ensure safety for both devices and personnel.
We’ll explore how standard breakers and GFCIs respond to ground fault currents and why standard breakers may leave you vulnerable to hazards compared to GFCIs.
Normal Operation
Consider the following sample lighting circuits, which are protected first by a standard circuit breaker and then by a GFCI circuit breaker.
In case of standard breaker, the light circuit is working properly as there is no overload or short circuit fault.
Click image or open in new tab to enlarge
In case of GFCI, the circuits operate normally as current in both Hot and Neutral is same. Hence, the light is functioning as expected.
Click image or open in new tab to enlarge
Short Circuit Fault
Consider a lighting circuit protected by a 15-amp standard circuit breaker. During a short circuit (where the hot wire touches the neutral or a metallic part of the device), the low resistance (0.2Ω) of the path allows a high current of approximately 600 amps to flow. This surge trips the 15-amp breaker, disconnecting the circuit from the power supply. This scenario illustrates the correct response of a circuit breaker to a short circuit.
Click image or open in new tab to enlarge
A GFCI circuit breaker also acts like a standard circuit breaker when a short circuit or overload occurs, but the operation is different. It detects the current difference between Incoming and outgoing current in Hot and Neutral. If both current are not equal, it suddenly trips to disconnect the circuit from the main power supply.
Click image or open in new tab to enlarge
But what happens during a ground fault or a lost neutral in the main panel when only a standard breaker is used? Let’s examine two scenarios.
- Broken Neutral
- Broken Neutral & Ground Faults
Broken Neutral
In Case of a Standard Breaker
If the neutral wire breaks in the main panel, current will flow back through the only available path to the transformer to complete the circuit. For example, if the load has a resistance of 20Ω and the ground path to the transformer has 30Ω, a current of 2.4 amps will flow. This low current is insufficient to trip the ordinary 15-20 amp breaker in the main or subpanel.
Click image or open in new tab to enlarge
Furthermore, all metal parts, including equipment and metal raceways, will be energized at 72 volts. If someone touches these parts while barefoot, they could receive a dangerous shock.
In Case of GFCI
To prevent this hazard, a GFCI breaker detects any current imbalance between the hot and neutral wires and trips, disconnecting the circuit from the main supply to ensure personnel safety.
Click image or open in new tab to enlarge
Broken Neutral & Ground Fault
In Case of Standard Breaker
Now, consider a worst-case scenario involving both a lost neutral and a ground fault. With no neutral in the main panel, current will seek an alternative path to complete the circuit, as the neutral and ground busbars are bonded in the main panel.
Click image or open in new tab to enlarge
In this situation, a current of 4 amps will flow through the 30Ω ground path back to the transformer. However, this current is still too low to trip a standard 15 or 20-amp breaker, which is commonly used for household appliances.
Again, all metal parts, including equipment and metal raceways, will be energized at 120 volts, posing a significant shock hazard to anyone who touches them while barefoot.
Related Posts:
- Why are Neutral and Ground Wires Separated in a Subpanel?
- Why Must Neutral and Ground Wires Be Bonded in the Main Panel?
- What Happens if the Neutral is Lost in the Main or Subpanel?
In Case of GFCI
In this scenario, a GFCI breaker detects the current imbalance caused by the lost neutral and immediately trips, providing protection and safeguarding personnel from potential shock hazards.
Click image or open in new tab to enlarge
Standard Circuit Breaker vs. GFCI:
Resources & Tutorials:
- National Electrical Code (NEC) Requirements for Panelboards
- How to Find the Right Wire Size for 100A Service 120V/240V Panel?
- How to Determine the Right Size Capacity of a Subpanel?
- How to Wire a Subpanel? Main Lug Installation for 120V/240V
- How to Determine the Number of Circuit Breakers in a Panel Board?
- How to Size a Load Center, Panelboards and Distribution Board?
- How to Wire 120V & 240V Main Panel? Breaker Box Installation
- How to Wire a GFCI Circuit Breaker?
- How to Wire and Install an Electrical Outlet Receptacle?
- How to Wire a GFCI Outlet?
- How to Wire GFCI Combo Switch and Outlet
- What Happens When You Touch an Electrical Busbar?
- Can the Neutral Wire Cause Electric Shock? Different Cases
- Difference Between Grounding, Earthing and Bonding
- Difference Between Neutral, Ground and Earth?
- Will I Get an Electric Shock If I Touch the Ground Wire?
- Will a Man Get an Electric Shock If He Hangs on a Live Wire?
- Difference Between Circuit Breaker and GFCI
- Tripping Curves of Circuit Breakers – B, C, D, K and Z Trip Curve