What is the Suitable Wire Size for 70A Breaker and Load?

How to Calculate the Correct Wire Size for a 70A Breaker and Load Circuits Based on NEC?

A 70-amp breaker are typically used for high-power devices like large HVAC systems, electric furnaces, and subpanels. These circuits must be carefully planned to ensure proper wire sizing for both safety and efficiency. In this article, we will explore how to select the appropriate wire size for a 70A breaker, based on the National Electrical Code (NEC).

The correct wire size for a 70-amp circuit is #4 AWG copper or #2 AWG aluminum, according to NEC tables. However, several factors influence wire size selection, including voltage drop, distance, insulation type, ambient temperature, and the type of conductor. Always consult a licensed electrician to verify compliance with the NEC and ensure the proper installation of your wiring system.

Correct Wire Size for 70-Amp Breaker

Factors Affecting Wire Size

When choosing the wire size for a 70-amp breaker and circuit, consider the following factors:

What is the Right Wire Size for a 70A Circuit?

According to NEC Table 310.15(B)(16), the appropriate wire size for a 70-amp circuit is:

The material of the conductor and factors like temperature and voltage drop will affect the exact wire size. Solid copper wire is often preferred over aluminum due to its higher conductivity and lower resistance.

The following shows the ampacity of #4 AWG copper and #2 AWG aluminum wire at different ambient temperatures:

#4 AWG Copper

#2 AWG Aluminum

It clearly shows that a #4 gauge copper or #2 gauge aluminum conductors can safely handles the required amount of electric current in amperes for a 70-amp breaker or fuse.

These values are based on NEC Table 310.15(B)(16). Consider the involved distance and ambient temperature ratings into account while selecting the right wire size.

Good to Know:

Selecting the Correct Wire Size for a 70A Breaker

Now, let’s break down how to choose the correct wire size for a 70A breaker and outlet for both continuous and non-continuous load circuits.

Continuous Load Circuit

For continuous loads (devices running for 3 hours or more), the NEC requires that the maximum current not exceed 80% of the breaker’s rating.

For a 70A breaker:

70A × 80% = 56A

This means the breaker should not be loaded with more than 56 amps continuously. If your device’s nameplate specifies a minimum circuit ampacity (MCA) of 56A, use the following formula to determine the appropriate breaker size:

56A × 125% = 70A

Thus, for a 70A breaker, a #4 AWG copper wire or #2 AWG aluminum wire is suitable, as it can carry the necessary current safely.

Non-Continuous Load Circuit

For non-continuous loads (such as general-purpose lighting or short-term use), the breaker can handle the full 70 amps without derating. In this case, both #4 AWG copper and #2 AWG aluminum are adequate wire sizes.

Related Post: What is the Suitable Wire Size for 50A Breaker and Outlet?

How Many Amps Can a 70A Breaker Safely Handle?

According to the NEC, a breaker should not be loaded beyond 80% of its capacity for continuous loads. Therefore, a 70A breaker can handle:

This complies with NEC Sections 210.19(A), 215.2, and 230.42(A).

Good to know:

How Many Watts Can a 70A Breaker Hold?

To calculate the wattage capacity of a 70A breaker, use the formula:

Watts = Volts × Amps

120V Circuit:

A 1-P, 70A breaker on a 120V circuit can hold:

Good to know: You may use a 70A breaker as a sub-panel to use more 15A, 20A,40A, etc. outlets for 120V circuits. According to the code, a 70A breaker for single unit should be wired with a disconnect switch.

240V Circuit:

A 2-P, 70A breaker in a 240V circuit holds:

You can connect safely up to 13,440 watts of load on a two pole, 70A breaker in a 240V circuit. You may use a single load up to 70A or multiple load circuits where the total amperes doesn’t exceed 70A.

Good to know: A 70A breaker can handle a maximum of 8,400W and safely 6,720W in a 120V circuit, while it can handle a maximum of 16,800W and safely 13,440W in a 240V circuit.

How Many Outlets Can Be Put on a 70A Breaker?

A 70A breaker is typically designed for a dedicated circuit serving a single high-power appliance. It is not recommended to wire multiple outlets to a 70A breaker, as this could overload the circuit. NEC Table 210.21(B)(3) restricts the number of outlets based on branch circuit size. A 70A breaker should only serve one high-power device.

However, it is permissible to use a 70A breaker as a sub-panel and use 15/20/30 amp breakers with associated and rated outlets as branch circuits.

Suitable Cable Types for a 70A Breaker

When selecting a cable for a 70-amp breaker, choose the appropriate insulation and wire type:

Applications of 70A Breakers

Common uses for 70-amp breakers include:

Related Post: What is the Correct Wire Size for a 40A Breaker and Load?

Good to Know: