What is the Correct Wire Size for a 40A Breaker and Load?

How to Determine the Suitable Wire Size for a 40A Breaker and Load Based on NEC?

Correct wire size selection for a 40A breaker and load circuit is crucial for the efficient, safe, and protected operation of both equipment and personnel. The wire and cable used in a 40-amp circuit must comply with the National Electrical Code (NEC), IEEE, IEC, or other applicable local standards.

A 40-amp breaker is a standard size available in 1-pole and 2-pole configurations for common 120V and 240V circuits. These breakers are used in high-power and heavy-duty circuits like EV charging, electric stoves and ranges, central air conditioning, or electric heating systems (HVAC). They protect cables rated at 40 amps or more and the circuit in case of overload or short circuit when the load circuit draws 40 amps or less during normal operation.

According to the NEC, the correct wire size for a 40-amp circuit is #8 AWG copper or #6 AWG aluminum. Keep in mind that the correct wire size depends on multiple factors such as distance, voltage drop, ambient temperature, type of cable and wire, type of insulation, etc. The following step-by-step guide will help you determine the suitable wire size for a 40-amp breaker and load circuits.

Correct Wire Size for 40A Breaker

Table of Contents

Toggle

What is the Suitable Wire Size for a 40A Breaker?

Based on NEC Table 310.15(B)(16) (formerly Table 310.16), the standard wire size for a 40-ampere breaker is #8 AWG copper wire.

If you use aluminum instead of copper with a 40A breaker, you typically need #6 AWG aluminum wire due to aluminum’s lower conductivity and high resistance compared to copper.

Both #8 AWG copper and #6 AWG aluminum wires can handle:

Due to the high power and amperage in the circuit, we recommend using #8 gauge solid copper wire instead of #6 gauge aluminum or stranded wire with 40A breakers and load circuits for safety, conductivity, and efficiency. Solid wire offers several advantages over stranded wire, which is why U.S. homes typically use solid rather than stranded wire.

Good to Know:

How to Select the Right Wire Size for a 40A Breaker and Load?

Selecting the right wire size involves several factors i.e. conductor material (copper or aluminum), circuit length and run, ambient temperature, and installation environment (e.g., indoor, outdoor, conduit). The following example shows the correct wire selection for 40A continuous and non-continuous load circuits:

Example:

Suppose you have installed a 40A (either 1-pole or 2-pole) breaker in the main panel or load center, and you need to wire it with a maximum of 40A load circuit. Follow the fowling simple steps to find the suitable wire size for a 40-Amp breaker and load circuits for both continuous and non-continuous load circuits according to NEC guidelines.

Continuous Load Circuit

The NEC’s 125% rule states that the maximum overcurrent protection device (MOCP) should handle 125% of the continuous load. As a safety factor, no more than 80% of the continuous load should be connected to the Overcurrent Protection Device (OCPD).

40A × 80% = 32A

Based on this rule, The amperes of the load circuit should not cross the maximum limit of 32A. In other words, you may only wire a 32-Amp of continuous load (lasts for 3-4 hours simultaneously) circuit to a 40-Amp breaker.

In second scenario where the minimum circuit ampacity (MCA) i.e. load circuit’s amperes are 32A, you may determine the correct breaker size for this circuit:

32A × 125% = 40A

According to NEC Table 310.15(B)(16), the #8 AWG wire size can carry 40A at 60°C (140°F) and 50A at 75°C (167°F).

Non-continuous Load Circuit

For non-continuous loads (e.g., general lighting circuits), the conductor size should be no less than 100% of the load. The same applies to overcurrent protection devices (OCPDs).

A 40A breaker can handle a maximum of 40A non-continuous load circuits, such as outlets and lighting points, while considering ambient temperature rating (Refer to 110.14(C) and 310.15(B)(2)).

How Many Amps Can a 40A Breaker Handle Safely?

A 40-amp breaker can safely handle a maximum of 40 amps of current. The NEC states that breakers should not exceed 80% of their rated capacity for continuous loads (lasting three hours or more). Therefore, a 40A breaker is suitable for a maximum of 32A continuous load circuits.

40A × 80% = 32A

For short, non-continuous loads, the breaker can handle up to 40 amps safely.

These ratings comply with NEC Sections 210.19(A), 215.2, and 230.42(A) for continuous and non-continuous loads, and 110.14(C) for ambient temperature.

The above calculations are based on NEC Table 310.15(B)(16) and 240.4(A) through (G), illustrating that the 8 AWG copper wire size can carry 40A at 60°C (140°F) and 50A at 75°C (167°F) which is the suitable size to use with a 40-Amp breaker.

How Many Watts Can a 40A Breaker Hold?

The power capacity of a 40-amp breaker can be calculated using the following formula:

120V Circuit

In a standard 1P, 120V circuit, the max power a 40A breaker can hold:

40 A × 120 V = 4,800 W

Applying the safety factor (80% Load):

40 A × 80% = 32 A

Hence, no more than 3,840 watts of load should be connected to a 40A breaker:

32A × 120V = 3,840 watts

It means, you may use 40A breaker with a 120V, 3.5kW to 3.8kW electric range or water heater element.

240V Circuit

A 2-P, 40A breaker in 240V circuit can hold the maximum power:

40 A × 240 V = 9,600 W

Applying the safety factor of 80% for continues load:

40 A × 80% = 32 A

Based on the calculation, you may connect up to 7,680 watts of load to a 2-pole, 240V, 40A breaker:

28A × 240V = 7,680 watts

For example, you may use a 40A breaker with a 240V, 7.5kW water heater element.

These calculations assume that the breaker is not continuously loaded to 100% of its capacity. For continuous loads, the safe wattage is 80% of these values:

How Many Outlets Can be Put on a 40A Breaker?

It is a good practice to use a 40-amp breaker for a dedicated circuit for high-power appliances, like electric ranges, water heaters, or large air conditioning units, instead of standard electrical outlets. The National Electrical Code (NEC) prohibits the use of standard 15-amp or 20-amp outlets (receptacles) with a 40-amp breaker because it would be unsafe.

When multiple general-purpose outlets are used on the circuit, a 40-Amp circuit breaker can support 18 outlets.

The NEC recommends that a circuit should not be loaded to more than 80% of its capacity to allow for safety margins. For a 40A breaker, the maximum continuous load should be:

40A × 0.8 = 32A

Theoretically, If each outlet is assumed to draw 1.5A, you can estimate the number of outlets by dividing the maximum continuous load by the per-outlet load:

32 A ÷ 1.5 A ≈ 21 outlets

Note that you should use a 40A breaker with one device and associated outlet at a time. For standard 15-amp or 20-amp outlets, use a 15-amp or 20-amp breaker, respectively. If you need a 40-amp breaker for a circuit, it’s likely intended for a single, dedicated appliance with a matching 40-amp receptacle. For more details, Refer to NEC Table 210.21(B)(3) for receptacle ratings for various circuit sizes.

If you need to install outlets, you should calculate the total expected load and ensure that the breaker and wiring are appropriately sized to protect the circuit and prevent overloading.

Is it Allowed to Use a 50A Outlet on a 40A Breaker?

In some special case, it is allowed to use a 50-amp receptacle on a 40-amp breaker. The safest practice is to ensure that both the breaker and outlet are rated for the same amperage. In simple terms, you should use a 40-amp breaker with a 40-amp rated outlet. Same is the case for 50A Breaker. It is good to keep in mind that the opposite scenario is not permitted i.e. it is permitted to use a 50A outlet on a 40A breaker, but it is not allowed to use a 40A outlet on a 50A breaker.

However, since NEMA standards do not include 40-amp outlets, let’s explore how to handle this situation.

According to the National Electrical Code (NEC), the breaker must match the amperage rating of the outlet to protect the wiring and devices connected to the circuit.

You might have seen Tesla Level 2 charging stations where a 40A breaker protects a 50A outlet, allowing for a maximum charging current of 32A.

This demonstrates that you can use a 50A receptacle on a 40A breaker under certain conditions:

  1. To wire a 50A receptacle and outlets (such as NEMA 14-50R or 6-50R) on a circuit with a 40A breaker, you must follow these conditions:
    • Ensure that the 50A outlet does not draw more than 40 amps for non-continuous loads when using a 40A breaker.
    • For continuous loads, the 50A outlet, when protected by a 40A breaker, must not draw more than 32A to comply with NEC rules for continuous load protection (80% rule).
  2. The breaker is designed to protect the wiring and prevent overheating. Using a 50A receptacle on a 40A breaker could cause confusion if there’s an issue or if someone attempts to use a device that draws more than 40 amps. Thus, the circuit must be clearly labeled to indicate that the 50A outlet is protected by a 40A breaker. This labeling ensures that maintenance electricians or future owners are aware of the exact setup for safety and proper protection.

Suitable Types of Cables for a 40-Amp Breaker

For a 40-amp breaker and outlet, the types of cables used must be capable of safely carrying the current without overheating. The choice of cable material and type depends on the installation environment and specific application. Here are the different types of cables typically used:

Copper Wire:

Aluminum Wire:

It is Used where lighter weight and cost are factors, such as in mobile homes or for certain high-amperage circuits. They Often used in industrial and commercial applications, particularly where high heat resistance is required.

Applications of a 40-Amp Breaker and Outlet

A 40-amp breaker is generally used in circuits that require a higher current than typical household outlets. Common applications include:

Good to Know:

Resources:

Exit mobile version