How to Wire a Garage Consumer Unit?

Wiring a Garage Consumer Unit with RCD & Connecting 1-Φ, 230V Load Points in it.

What is a Garage Consumer Unit?

A Garage Consumer is a type of consumer unit and distribution board (aka mini consumer unit) used to extend and provide electric supply to the exterior buildings such as shed, workshop or other outdoor installations in the garage.

A garage consumer unit is used to feed up fewer load circuits (generally 2-5 units). If only a small amount of load points are needed to power up through mains supply, they install a garage consumer unit instead of larger consumer units especially in outbuildings.

A garage fuse box is simple to install, troubleshoot and repair due to the simplicity and basic design with top hinged door. Generally, there is a 40A, 2-Poles RCD and other related circuit breakers such as 6A, 16A, 32A MCB (circuit breakers) based on the system requirements.

In this tutorial, we will be showing how to install a single phase garage consumer unit for 230V with RCD’s according to IEC. We will be using the IEC wiring color codes which is also applicable to EU, UK and other countries.

Click image to enlarge

Wiring a Garage Consumer Unit

Components Needed:

Related Posts:

How to Wire a Garage Consumer Unit?

To connect the rated MCB’s and RCD in the garage consumer unit for specific appliances, follow the following simple steps.

Click image to enlarge

How to Wire a Garage Consumer Unit

You have done, the electrical appliances now can be connected to the new wired consumer unit and its MCB’s via three wires i.e. Brown as Live “L”, Blue as Neutral “N” and Protective Earth “E” as Green with Yellow Stripe.

You may now restore back the power supply by turning ON the main switch or related circuit breaker in the consumer unit and test if it is working perfectly.

Related Post:

How to Connect Load Circuits in the Garage Consumer Unit

To connect a single phase 230V AC load circuit to the newly installed garage consumer unit, keep in mind that the Live should be taken from the output terminals of MCB and Neutral and Earth from the Neutral & Earth Busbar terminals in the CU respectively.

Moreover, you may use RCBO’s with RCD instead of single pole MCB if needed. Also, don’t connect the lighting points and three pin sockets to the same MCB. This way, the light bulbs will still glow if a fault occurs on the three pin socket which will trip the desired MCB. In the above case, you may connect the lighting points to the 6A MCB while the dual socket (for immersion heaters or dedicated freezer circuits) to the 16A MCB. Similarly, the 32A breaker can be used for electric ranges, electric showers and other high power devices.

Click image to enlarge

Wiring Load Circuits in the Garage Consumer Unit

Good to know: According to IET (Institution of Engineering and Technology) wiring regulations: 17th Edition (BS 7671:2008 – 1: 2011), an RCD protection must be provided in the consumer unit except smoke and burglar alarms system.

Related Posts:

IEC & UK Wiring Color Codes:

We have used the following IEC wiring color codes for 230V single phase  supply voltage applicable in the UK and EU. The United Kingdom was using their own wiring color codes (prior April, 2004) while some countries are still following the same old UK wiring color code. The United Kingdom is following IEC wiring color codes now.

IEC Wiring Color Codes for 230V, 1-Phase, 3-Wire System: EU & UK

Old UK Wiring Color Codes for Single Phase, 230V AC

230V Single Phase

Related Posts:

Instruction & Safety Precautions

Related Wiring Installation Tutorials:

Exit mobile version