In Inductive Circuit, Why the Power Factor (Cos θ) Decreases, When Inductance (L) or Inductive reactance (XL) Increases?
Next question from electrical and electronics engineering interviews question and answers series.
Explain the statement that “In an inductive circuit, when inductance (L) or inductive reactance (XL) increases, the Circuit power factor (Cos θ) decreases“.
- Related Post: Why Power Factor Decreases When Capacitive Reactance Increases or Capacitance Decreases?
Explanation:
We know that in DC circuits:
I = V / R,
But in case of AC circuits:
I = V / Z
Where “total resistance of AC circuits = Impedance = Z = √ (R2 + (XL – XC2)”
In case of Inductive circuit:
- Z = √ (R2 + XL2)
- I = V / XL or I = V / Z
Related Questions:
- Why Current Increases When Capacitance Increases or Capacitive Reactance Decreases?
- Why Current Decreases When Inductance or Inductive Reactance Increases?
It shows that in an inductive circuit, current is inversely proportional to the inductive reactance as well as inductance “L” as inductance and inductive reactances “XL” are directly proportional to each others. It means, if inductance increases, the circuit current decreases which leads to decrease the power factor. Similarly, when the circuit current increases due to decrease in inductance or inductive reactance, the overall power factor will be improved as power factor is directly proportional to the inductance and inductive reactances.
Let’s check with a solved example to see how power factor decreased by increase in inductance and inductive reactance.
When Inductance = 0.01 H
Suppose an inductive circuit where:
- Inductance = L = 0.01 Henry
- Voltage = V = 230 V
- Resistance = R = 12 Ω
- Frequency = f = 60 Hz
To find the inductive reactance;
XL = 2πfL
XL = 2 x 3.1415 x 60 x 0.01
XL = 3.77 Ω
Now circuit impedance:
Z = √ (R2 + XL2)
Z = √ (122 + 3.772)
Z = 12.58 Ω
Finally, Power factor in inductive circuit:
Cos θ = R / Z
Cos θ = 12 Ω / 12.58 Ω
Cos θ = 0.95
- Related Question: Why Power in Pure Inductive and Pure Capacitive Circuit is Zero?
When Inductance = 0.03 H
Now we increased the Inductance (L) of inductor form 0.01 H to 0.03 H.
V = 230 V, R = 12 Ω, L = 0.03 H, f = 60 Hz.
XL = 2πfL= 2 x 3.1415 x 60 x 0.03 = 11.30 Ω
Z = √ (R2 + XL2) = √ (122 + 11.302) = 16.48 Ω
Power Factor = Cos θ = R / Z = 12 Ω / 16.48 Ω
Cos θ = 0.73
Related Questions:
- In a Capacitive Circuit, Why the Current Increases When Frequency Increases?
- In an Inductive Circuit, Why the Current Increases When Frequency Decreases?
Conclusion:
We can see that, when inductance (L) was 0.01 Henry, then circuit power factor were 0.95,
But when circuit inductance increased from 0.01 H to 0.03 H, then the power factor decreased from 0.95 to 0.73.
Hence proved,
In an inductive circuit, when inductance or inductive reactance XL increases, the circuit power factor decreases and vice versa.
In oral or verbal,
- Inductive reactance is a kind of resistance. When inductive reactance increases, the circuit power factor decreases and vice versa.
- Inductance is directly proportional to the inductive reactance
L ∝ XL
- Inductance is directly proportional to the inductive reactance and current.
L ∝ I and L ∝ XL
- Power factor is inversely proportional to the inductance and inductive reactance.
Cos θ ∝ 1/L and Cos θ ∝ 1/XL
Related Questions/Answers:
- Why Flux in Primary and Secondary Winding is Always Equal?
- Why the reactance of a system under fault condition is low and faults currents may raise to the dangerously high value?
- Why Inductive Reactance (XL In DC Supply Is Zero (0)?