In Capacitive Circuit, Why the Circuit Current (I) Increases, When Capacitance (C) Increases or Inductive Reactance (XC) Decreases?
Next question from electrical and electronics engineering interviews question and answers series.
Explain the statement that ” In a capacitive circuit, when Capacitance (C) increases or capacitive reactance (XC) decreases, the Circuit Current (I) decreases“.
Related Question: Why Current Decreases When Inductance or Inductive Reactance Increases?
Explanation:
We know that in DC circuits:
I = V / R,
But in case of AC circuits:
I = V / Z
Where “total resistance of AC circuits = Impedance = Z = √ (R2 + (XL – XC2)”
In case of Capacitive circuit:
- Z = √ (R2 + XC2)
- I = V / XC or I = V/Z
It shows that in a capacitive circuit, Current is inversely proportional to the capacitive reactance as well directly proportional to the capacitance “C” as capacitance and capacitive reactances “XC” are inversely proportional to each others.
Let’s check with an example to see how current reduced by capacitive reactance and increased by increasing the value of capacitor.
When Capacitance = 10 µF
Suppose a capacitive circuit where:
- Capacitance = C = 10µ Farads
- Voltage = V = 220 V
- Frequency f = 50 Hz
To find the capacitive reactance;
XC = 1 / 2πfC
XC = 1 / (2 x 3.1415 x 50 x 10×10-6)
XC = 318.3 Ω
Finally, current in capacitive circuit:
I = V / XC
I = 230V / 318.3 Ω
I = 0.72 A
Related Questions:
- Why Power Factor Decreases When Inductance or Inductive Reactance Increases?
- Why Power Factor Decreases When Capacitive Reactance Increases or Capacitance Decreases?
When Capacitance = 60 µF
Now we increased the value of capacitance (C) of a capacitor form 10 µF to 60 µF.
V = 220V, C = 60 µF, f = 50 Hz.
XC = 1 / 2πfC = 2 x 3.1415 x 50 x 60 µF = 53 Ω
I = V / XC = 230 V / 53 Ω
I = 4.34 A
Related Questions:
- In a Capacitive Circuit, Why the Current Increases When Frequency Increases?
- In an Inductive Circuit, Why the Current Increases When Frequency Decreases?
Conclusion:
We can see that, When capacitance (C) was 10µF, then circuit current were 0.72 A,
But when circuit capacitance increased from 10 µF to 60 µF, then the current increased from 0.72 A to 4.34 A.
Hence proved,
In a capacitive circuit, when capacitance increases, the capacitive reactance XC decreases which leads to increase the circuit current and vise versa.
In oral or verbal,
- Capacitive reactance is a kind of resistance. When resistance increases, the circuit current decreases and vice versa.
- Capacitance is inversely proportional to the capacitive reactance.
C ∝ 1 / XC
- Current is directly proportional to the capacitance and inversely proportional to capacitive reactance.
I ∝ C and I ∝ 1/XC
Related Questions/Answers:
- Why Flux in Primary and Secondary Winding is Always Equal?
- Why the reactance of a system under fault condition is low and faults currents may raise to the dangerously high value?
- Why Inductive Reactance (XL In DC Supply Is Zero (0)?

Should GFCI Protection Be in the Main Panel or Receptacle?
Why Does the High Leg Measure 208V Instead of 120V?
Why are 1-Phase Motors Not Self-Starting Like 3-Phase Motors?
Why are High-Power Devices Not Designed to Run on DC Voltage?
How Do Some Devices Have Dual Input Voltage Ratings?
Why is AC Commonly Used in Households Instead of DC?